Dampak Tegangan Induksi Petir pada Tangki Penyimpanan Bahan Bakar Cair Flammable

  • Budi utama Sekolah Tinggi Teknologi Nasional

Abstract

ABSTRACT

This paper analyses the induced voltage of the lightning that accumulated into the body  of the  fuel tank structure, moment  after a lightning stroke hit the rod of lightning protection  at the top of  its protection tower. The protection mast and the lightning rod are 33 m and 6 m in heigh respectively. The Calculation of the induced voltage were simulated  and carried out using Matlab software for finding the shape impulse wave and magnitude of the inducing voltage of the lightning that were accumulated in the tank structure. This analysis depicts that the lightning induction voltage varies with the distance between the lightning rod position and tank location, so that any changes in the induced voltage value are followed by changes the limitation of the minimum air gap in the tank.The results are very important to know the parameters that causes a fire and an incendive spark in the tank.

Published
2019-11-04
How to Cite
utama, B. (2019) “Dampak Tegangan Induksi Petir pada Tangki Penyimpanan Bahan Bakar Cair Flammable”, ReTII, pp. 306-316. Available at: //journal.itny.ac.id/index.php/ReTII/article/view/1187 (Accessed: 27December2024).