A Hybrid Newton-Raphson Unbalanced Three-Phase Loadflow and Rotor’s qd0 Reference Frame of Syncronous Generator Model as An Alternative Tool for Studying The Impact of Unbalanced Loads on Power Angle Change of Three Phase Synchronous Generator Connecte
Abstract
The issues considering power system dynamics are often studied by looking at the dynamic responses of generators
connected through the power grid, taking their interactions into consideration. This work decribes a specific study on the impact
of unbalanced loads of the grid on rotor angle change of synchronous generators under steady state condition with quantitive
evidence. Since the dynamic interactions are usually characterized by both grid-structure-related and status-related variables, an
accurate portrait of the dynamic behavior of synchronous generators under unbalanced conditions can be described by a
complex nonlinear differential-algebraic model. In this paper, an alternative tool for studying such dynamic behaviour was
created by hybrid Newton-Raphson unbalanced three-phase loadflow and rotor’s qd0 reference frame of synchronous generator.
Active windows with this generator model based on qd0 framework were developed using Visual’s Graphical User Interface
(GUI) capability to examine the rotor angle of the machine after small perturbations, focusing on electromagnetically dynamic
as affected by load unbalance. Newton-Raphson unbalanced loadflow was used to derive the generator’s terminal inputs through
load-flow analysis on the grid. The results showed that the significant influence of unbalanced loads occured in power angle.
Prosiding ini memberikan akses terbuka langsung ke isinya dengan prinsip bahwa membuat penelitian tersedia secara gratis untuk publik mendukung pertukaran pengetahuan global yang lebih besar.
Semua artikel yang diterbitkan Open Access akan segera dan secara permanen gratis untuk dibaca dan diunduh semua orang.